Indirect Heat Interface Unit – Heating only

HYDRAULIC CIRCUIT
HT30/45 Hydraulic Circuite
HYDRAULIC CIRCUIT COMPONENTS
1. Insulated brazed plate heat exchanger
2. Ultrasonic energy meter G 1” – 130mm
3. Sensor pocket for heat meter
4. Filter
5. Pressure independent control balancing valve with 230V electric actuator
6. Expansion tank
7. Manual air vent valve
8. Ball valve
9. Manometer
10. Flow regulator with load and washing system
11. 3 bar safety valve
12. High efficiency Wilo pump
13. Loading system
CONNECTIONS
DHS District heating supply G 1” (int. thread)
DHR District heating return G 1” (int. thread)
HR Heating return G 1” (int. thread)
HS Heating supply G 1” (int. thread)
GENERAL DATA
Max pressure: 10 bar
Max supply temperature: 85°C
Min temperature: 5°C
Weight: HT30 24kg, HT45 25kg
Electrical supply: 230 V
Dimensions with cover (H x W x D): 835 x 475 x 226mm